An induction motor does two jobs at once: it turns electrical power into mechanical work, and it builds the magnetic field that makes that possible. The first job draws real power, measured in watts. The second draws reactive power, measured in VAR — current that sloshes back and forth between the supply and the motor without doing any work, but which still has to travel through the cables, the switchgear and the meter. A motor running at a power factor of 0.7 draws 43% more current than the same motor at unity power factor. One capacitor, wired in parallel with the motor, can take most of that extra current away. This article sizes it for a real 2 kW motor and works out every number.
Figure 1: The correction capacitor (a) sits in parallel with the motor and supplies its reactive current locally, so the supply only carries the real current. The line current falls from 12.42 A to 9.15 A (b). (Schematic, not to scale.)
How it works — the formulas
Real power P does the work; apparent power S = V × I is what the supply must deliver; reactive power Q builds the magnetic field. The three form a right-angled triangle, and the power factor is the cosine of the angle between P and S:
S = P / pf, I = S / V, Q = P × tan φ, φ = cos⁻¹(pf)
A capacitor connected across the supply draws a leading reactive power Qc that cancels part of the motor's lagging Q. The real power P does not change, so the new reactive power is Q2 = Q1 − Qc, and the capacitor value follows from Qc = V² × 2Ï€f × C:
Qc = P × (tan φ1 − tan φ2), C = Qc / (2Ï€f × V²)
The reward is quadratic: cable and transformer losses are I²R, so a 26% drop in current cuts those losses by nearly half.
Worked example — correcting a 2 kW motor from 0.7 to 0.95
Take a 230 V, 50 Hz single-phase motor delivering P = 2 kW at pf1 = 0.7 lagging. Before correction the apparent power is S1 = 2000 / 0.7 = 2857 VA, so the line current is I1 = 2857 / 230 = 12.42 A. The angle is φ1 = cos⁻¹(0.7) = 45.57°, tan φ1 = 1.0202, so the motor's reactive power is Q1 = 2000 × 1.0202 = 2040 VAR.
Correct it to pf2 = 0.95: φ2 = cos⁻¹(0.95) = 18.19°, tan φ2 = 0.3287, so the remaining reactive power is Q2 = 2000 × 0.3287 = 657 VAR. The capacitor must supply Qc = 2040 − 657 = 1383 VAR, and its value is C = 1383 / (2Ï€ × 50 × 230²) = 1383 / 16,619,064 = 83.2 µF — use the nearest standard motor-run value, 80 µF or 85 µF. The capacitor carries Ic = Qc / V = 1383 / 230 = 6.0 A of its own, but that current circulates between the capacitor and the motor, not through the supply cable.
After correction the apparent power is S2 = 2000 / 0.95 = 2105 VA and the line current is I2 = 2105 / 230 = 9.15 A — a drop of 26.3%. If the supply cable has 0.5 Ω of resistance, its loss falls from 12.42² × 0.5 = 77.1 W to 9.15² × 0.5 = 41.9 W, saving 35.2 W of heat in the cable alone — a 45.7% cut in losses, since (9.15/12.42)² = 0.543.
The catch — never use an ordinary capacitor, and never over-correct
Two traps. First, the capacitor sits directly across the 230 V mains, so it must be a motor-run capacitor rated for continuous AC duty — typically 440 V AC — with a self-healing metallised film construction. An electrolytic or a low-voltage DC capacitor will fail, sometimes violently. The peak voltage it sees is 230 × √2 = 325 V, and mains transients go higher, which is why the 440 V rating is the standard choice. Second, do not correct all the way to unity or beyond: a leading power factor can push the voltage up at light load (the Ferranti effect on a long feeder) and many utilities penalise leading power factor just as they penalise lagging. The usual target is 0.95 lagging, exactly as in this example. And size the capacitor for the motor's actual running load — a capacitor sized for full load over-corrects when the motor idles, because the real power drops while the capacitor's reactive power stays the same.
Why the electricity board cares
The motor still consumes the same 2 kW of real power, so the energy meter — which bills kWh — does not spin any slower. The saving is in the infrastructure: the supply cable, the transformer and the generator all carry less current, so their I²R losses fall and more capacity is freed for other loads. That is why utilities charge industrial consumers a penalty below a set power factor (often 0.9) and sometimes offer a rebate above it. For a factory with many motors, a single capacitor bank at the main board does the same job for the whole plant — the principle is identical, only the arithmetic is done on the total load.
Key points to remember
- Power factor is cos φ: at pf 0.7 a 2 kW motor draws S = 2857 VA and I = 12.42 A on 230 V, with Q = 2040 VAR of reactive power doing no work.
- Worked example: correcting 0.7 → 0.95 needs Qc = 1383 VAR, so C = 83.2 µF; the line current falls to 9.15 A (down 26.3%) and cable losses fall 45.7%.
- The capacitor supplies the motor's reactive current locally — it carries 6.0 A of its own, but that current never travels through the supply cable.
- Use a 440 V AC motor-run capacitor (the 230 V RMS mains peaks at 325 V) — never an electrolytic or DC-rated capacitor across the mains.
- Target 0.95 lagging, not unity: over-correction gives a leading power factor, raises voltage at light load, and can attract the same penalty.
- Correction does not change the kWh on the bill — it cuts I²R losses and frees supply capacity, which is why utilities penalise a low power factor.