Reactance Relay and the R–X Plane: Why Arc Resistance Does Not Fool It

Author: Abloom Spark Date: November 07, 2026

A distance relay measures the impedance to the fault and trips if it falls inside its zone. The trouble is that a fault arc adds resistance, which shifts the measured impedance sideways on the R–X plane — and an impedance relay can be fooled into seeing the fault as further away than it really is. The reactance relay solves this by measuring reactance only. This post explains how, and what its characteristic looks 

like.



Figure 6.1: Reactance relay on the R–X plane: X = Xset is a horizontal line. Arc resistance Rarc shifts the measured impedance sideways, but it stays below the line. (Schematic, not to scale.)

Torque and the balance condition

A reactance relay develops operating torque from the current (K1I²) and restraining torque from a voltage–current directional element with Ï„ = 90° (K2VI sin θ), plus a spring restraint K3. The relay operates when:

T = K1·I² − K2·V·I·sin θ − K3 ≥ 0

At the balance point, K1I² = K2VI sin θ. Dividing by I² gives Z·sin θ ≤ K1/K2, that is:

X = Xset

The characteristic: a horizontal line

On the R–X plane, X = Xset plots as a horizontal straight line parallel to the R-axis. Everything below the line (X < Xset) is the trip zone; everything above it (X > Xset) is the block zone.

This is the relay's great strength: it is completely immune to fault arc resistance Rarc. Arc resistance adds pure resistance, so it moves the measured impedance sideways — along the R direction — but the reactance X does not change, and the point stays below the line. The relay still trips correctly for a fault at the end of its zone, no matter how much arc resistance the fault has.

That makes the reactance relay ideal for short lines, where the line reactance is small and arc resistance is a large fraction of the total fault impedance. On a long line the same property becomes a weakness — the relay can overreach for faults beyond its zone when the line's own resistance is significant — so it is used where lines are short and arc resistance dominates.

Key points to remember

  • Torque: T = K1I² − K2VI sin θ − K3 ≥ 0; at balance, Z·sin θ = X = Xset.
  • The characteristic is a horizontal straight line parallel to the R-axis on the R–X plane.
  • Trip zone: X < Xset. Block zone: X > Xset.
  • Immune to arc resistance Rarc — it only shifts the impedance sideways, never above the line.
  • Ideal for short lines, where arc resistance is a large part of the fault impedance.

Based on Power System Protection & Switchgear.