Resistance Switching: Sequence of Operation and Why ABCBs Need It

Author: Abloom Spark Date: November 07, 2026

When a circuit breaker interrupts a small inductive current — for example, switching off an unloaded transformer or a shunt reactor — the current can be chopped off suddenly before its natural zero. The magnetic energy stored in the inductance then has nowhere to go, and the voltage across the breaker contacts can rise violently. This is the problem resistance switching solves: a shunt resistor connected across the breaker contacts absorbs that energy and damps the transient. This post explains the switching sequence and why the air blast circuit breaker (ABCB) needs it more than any other breaker.

What resistance switching is

In resistance switching, a resistor R is connected in parallel with the main contacts of the circuit breaker. The resistor is switched in and out by a small auxiliary contact (aux switch) that operates a few milliseconds after the main contacts. The resistor is not in the circuit during normal service — it is only brought in for the brief moment of interruption, to absorb the stored energy and to damp the transient recovery voltage (TRV).



Figure 3.2: Resistance switching circuit (left) and damping of the transient recovery voltage (right). Without R the TRV oscillates up to 2Vm; with the critical value R = 0.5√(L/C) it is damped to Vm. (Schematic, not to scale.)

Sequence of operation

  1. Main contacts open first. As the main contacts separate, an arc is drawn between them, and the fault (or load) current keeps flowing through the arc.
  2. At current zero, the main arc extinguishes. At that instant the fault current diverts into the parallel shunt resistor R. The resistor does two things: it critically damps the high-frequency L–C transient when its value is R = 0.5√(L/C), and it raises the power factor of the circuit, so the current that remains is smaller and much easier to interrupt.
  3. A few milliseconds later, the auxiliary contact opens. It interrupts the reduced, high-power-factor resistor current — a far easier duty than interrupting the original fault current — and the resistor is taken out of circuit.

The key number is the critical damping value, R = 0.5√(L/C), where L is the system inductance and C is the stray capacitance across the breaker. With this value the TRV rises smoothly to the supply peak Vm instead of oscillating up to 2Vm, as the right-hand graph shows.

Why the air blast circuit breaker needs it

Resistance switching is used most in the ABCB, for two reasons that come straight from how an air blast breaker works:

  • The air-blast pressure is fixed and independent of the current magnitude. In an oil breaker or an SF6 breaker, the arc itself helps to generate the interrupting pressure, so the blast is naturally weaker on small currents. In an ABCB the blast is the same whether the current is 20 kA or 20 A — so on a small inductive current the powerful blast chops the current off abruptly, long before its natural zero. That is severe current chopping.
  • Air is highly sensitive to a steep rate of rise of recovery voltage (RRRV). After chopping, the voltage across the contacts rises very fast; if it rises faster than the air gap can recover its dielectric strength, the arc restrikes. The shunt resistor dissipates the stored magnetic energy (½LI²) and damps the RRRV below the dielectric recovery rate of air.

In short: the ABCB's fixed, powerful blast creates the chopping problem, and the shunt resistor is the cure — it turns a violent, high-frequency transient into a gentle, damped rise.

Key points to remember

  • Resistance switching = a shunt resistor R across the main contacts, switched by an auxiliary contact a few ms after the main contacts.
  • Sequence: main contacts open → arc extinguishes at current zero → current diverts into R → aux switch opens the reduced current.
  • Critical damping when R = 0.5√(L/C): TRV is damped to Vm instead of oscillating to 2Vm.
  • ABCB needs it most because its blast pressure is fixed regardless of current, causing severe current chopping on small inductive currents.
  • The resistor dissipates the stored energy ½LI² and keeps the RRRV below air's dielectric recovery rate.

Based on Power System Protection & Switchgear.